Metal Clad (MCHL) cable 용 Hawke 711 Series

 

안녕하세요 TIATIP 입니다.

 

오늘은 Metal Clad (MCHL) cable 용으로 사용되는 Hawke 711시리즈를 소개합니다.

 

 

 

 

Cable Glands 711

North American Cable Glands/Connectors

Explosion Proof

IECEx and ATEX Approved Flameproof Exd,

Increased Safety Exe and Restricted Breathing ExnR

(Note : Dual Marked UL & ATEX as standard).

 

Application

- Outdoor or indoor use.

- For use with continuous corrugated aluminium Metal Clad (MCHL) cable.

 

 

 

 

 

Features

Provides 360° armour grounding which is fully inspectable.
Grounding device remains in contact with the cable when disassembled for inspection.
Provides a barrier seal between the individual insulated cores within the cable and prevents entry of the products of an explosion into the cable.
Assembly of the cable gland/connector compresses and distributes the compound evenly to create a barrier seal at the point of entry into the enclosure.
Provides an outer deluge seal to prevent moisture ingress to the cable armour and enclosure. Deluge seal is coloured red to indicate hazardous locations product.
Provides a cable retention and low smoke and fume, zero halogen seal onto the cables outer jacket.

 

Materials & Finishes

The 711 cable gland/connector is manufactured in Brass (standard), Nickel Plated Brass, 316 Stainless Steel or Aluminum.
Brass NPT entries are nickel plated as standard.

 

Technical Data

UL Listing No: E84940.
Suitable for use in:
Class 1, Division 1, Gas Groups A, B , C and D.
Class 1, Zone 2, Gas Groups IIA, IIB and IIC.
AExd IIC and AExe II Class 1, Zone 2.
Flameproof Exd, Increased Safety Exe  II 2 GD and Restricted Breathing ExnR  II 3G.
Sira Certificate No. Sira 06ATEX1295X
IECEx Certificate NO. IECEx Sir 06.0082X
Suitable for use in Zone 1, Zone 2, Zone 21, Zone 22 and in Gas Groups IIA, IIB and IIC.
Construction and Test Standards: UL 2225, IEC/EN 60079-0, IEC/EN 60079-1, IEC/EN 60079-7, IEC/EN 60079-15, IEC/EN 61241-0 and IEC/EN 61241-1.
Ingress Protection: IP66, IP67 and IP 68 (30 metres for 7 days) to IEC/EN 60529 and NEMA 4X.
Deluge protection to DTS01..
Operating Temperature Range: -50°C to +60°C (UL) and -60°C to +80°C (ATEX / IECEx).
Note: 711 cable glands are supplied dual ATEX/UL marked as standard.

 

 

주문품번체계는 다음과 같습니다.

 

(1) NPT형식

HAWKE 711/A/NPT1/2"

HAWKE 711/A/NPT3/4"

HAWKE 711/B/NPT3/4"

HAWKE 711/B/NPT1"

HAWKE 711/C/NPT1"

HAWKE 711/C/NPT1-1/4"

HAWKE 711/C2/NPT1-1/4"

HAWKE 711/C2/NPT1-1/2"

HAWKE 711/D/NPT2"

HAWKE 711/D/NPT1-1/2"

HAWKE 711/E/NPT2"

HAWKE 711/E/NPT2-1/2"

HAWKE 711/F/NPT3"

HAWKE 711/F/NPT2-1/2"

HAWKE 711/H/NPT3-1/2"

 

(2) ISO METRIC형식

HAWKE 711/A/M20

HAWKE 711/B/M25

HAWKE 711/C/M32

HAWKE 711/C2/M40

HAWKE 711/D/M50

HAWKE 711/E/M63

HAWKE 711/F/M75

HAWKE 711/H/M90

 

 

 

 

 

Hawke 711.pdf