Hawke 710 Cable Gland/Connector

 

안녕하세요 TIATIP 입니다.

 

오늘 이 시간에는 호크, Hawke의 North American Cable Glands/Connectors Type의 710시리즈를 살펴봅니다.

 

 

 

 

Application

Outdoor or indoor use.
For use with non-armoured cable, as permitted by the NEC.

 

Features

Provides a barrier seal between the individual insulated conductors within the cable and prevents entry of the products of an explosion into the cable.
Assembly of the cable gland/connector compresses and distributes the compound evenly to effect a barrier seal at the point of entry into the enclosure.
Provides an outer deluge seal to prevent moisture ingress to the cable armour and enclosure. Deluge seal is colored red to indicate hazardous locations product.
Provides a cable retention and low smoke and fume, zero halogen seal onto the cables outer jacket.

 

Materials & Finishes

The 710 cable gland/connector is manufactured in Brass (standard), Nickel Plated Brass, 316 Stainless Steel or Aluminum.
Brass NPT entries are nickel plated as standard.

 

Technical Data

UL Listing No: UL Certificate E84940.
Suitable for use in:
Class 1, Division 2, Gas Groups A, B , C and D.
Class 1, Zone 2. Gas Groups IIA, IIB and IIC.
AExd IIC and AExe II Class 1, Zone 2.
Flameproof Exd, Increased Safety Exe  II2 GD and Restricted Breathing ExnR  II 3G
Sira Certificate No. Sira 06ATEX1295X
IECEx Certificate NO. IECEx Sir 06.0082X
Suitable for use in Zone 1, Zone 2, Zone 21, Zone 22 and in Gas Groups IIA, IIB and IIC.
Construction and Test Standards: UL 2225, IEC/EN 60079-0, IEC/EN 60079-1, IEC/EN 60079-7, IEC/EN 60079-15, IEC/EN 61241-0 and IEC/EN 61241-1.
Ingress Protection: IP66, IP67 and IP 68 (30 metres for 7 days) to IEC/EN 60529 and NEMA 4X.

Deluge protection to DTS01.
Operating Temperature Range -50°C to +60°C (UL) and -60°C to +80°C (ATEX / IECEx).
Note: 710 cable glands are supplied dual ATEX/UL marked as standard.

 

 

 

 

 