호크 Hawke ICG 653/Universal/L Cable Gland 기술사양

 

안녕하세요 TIATIP 입니다.

 

앞서 소개드렸던 Hawke ICG 653/Universal 시리즈의 기본사양에 Lead Inner Sheath 에 적합하도록 구성된 케이블글랜드 입니다.

 

 

Hawke

Cable Glands

ICG 653/Universal/L Cable Gland

Group II Hazardous Area

Flameproof Exd / Increased Safety Exe / Dust Extb /

Dual Certified ATEX - IECEx

 

 

 

 

 

Application

Outdoor or indoor use.
For use with single wire armour ‘W’, wire braid ‘X’ and steel tape armour ‘Z’ elastomer and plastic insulated cables with a lead inner sheath.
For particular use with:-
a) Cables that are not effectively filled, compact and/or circular, have tape bedding or have hygroscopic fillers.
b) Cables that exhibit 'cold flow' characteristics.
c) Enclosures containing an ignition source in gas group IIC areas or containing an ignition source in a Zone 1 area and exceeding 2 litres in volume.

 

 

 

 

 

Features

Provides a barrier seal between the individual insulated cores within the cable and prevents entry of the products of an explosion into the cable.
Assembly of the cable gland compresses and distributes the compound evenly to create a barrier seal at the point of entry into the enclosure.
The compound chamber may be separated from the cured compound to ensure that the chamber has been effectively filled. If required, external voids can be repaired.
Provides armour clamping, using one clamping arrangement for all armour/braid types.
Provides a seal and an electrical bond on the cables lead inner sheath.
Provides an outer deluge seal to prevent moisture ingress to the cable armour/braid.
Provides a cable retention and low smoke and fume, zero halogen seal onto the cables outer sheath.

 

 

 

 

 

Materials & Finishes

The ICG 653/Universal/L cable gland is manufactured in Brass (standard), Nickel Plated Brass, 316 Stainless Steel or Aluminum. Brass NPT entries are nickel plated as standard.

 

 

Technical Data

1.Exd IIC Gb, Exe II Gb, Extb IIIC Db

2.Certificate No's Baseefa06ATEX0058X and IECEx BAS 06.0015X.

3.Suitable for use in: Zone 1, Zone 2, Zone 21, Zone 22 and in Gas Groups IIA, IIB and IIC.

4.Construction and Test Standards: IEC/EN 60079-0, IEC/EN 60079-1, IEC/EN 60079-7, IEC/EN 61241-0 and IEC/EN 61241-1.

5.Ingress Protection: IP66, IP67 and IP68 (30 metres for 7 days) to IEC/EN 60529 and NEMA 4X.

6.Deluge Protection to: DTS01

7.Operating Temperature Range: -60°C to +80°C

8.Assembly Instruction Sheet: AI 301 & AI 336.

 

ICG653 Universal L Spec.pdf

ICG653 Universal L Assembly 01.pdf

2.Hawke Accessories 2013 IDK.pdf

 

 

 

 

 

 

Hawke Ordering Format

[Gland Type/Size/Thread/Options]

Example without options : ICG 653/UNIV/C/M32/L

Example with alternative clamping ring options :

ICG 653/UNIV/C/1-1/4"NPT/L/AR

 

 

 

 

 