호크 Hawke CSB 656N Cable Gland 기술사양

 

안녕하세요 TIATIP 입니다.

 

Hawke Conduit System 의 CSB 656N Cable Gland 에 대해 살펴보도록 하겠습니다.

 

 

 

Hawke

Cable Glands

CSB 656N Cable Gland

Group II Hazardous Area

Flameproof Exd / Increased Safety Exe / Dust Extb /

Dual Certified ATEX - IECEx

 

 

 

 

 

 

 

Application

Outdoor or indoor use.
For use with conduit incorporating individual insulated conductors or for particular use with:-
a) Cables that are not effectively filled, compact and/or circular, have tape bedding or have hygroscopic fillers.
b) Cables that exhibit 'COLD FLOW' characteristics.
c) Enclosures containing an ignition source in gas group IIC areas or containing an ignition source in a Zone 1 area and exceeding 2 litres in volume.

 

 

 

 

 

Features

Provides a barrier seal between the individual insulated cores within the cable and prevents entry of the products of an explosion into the cable or conduit.
Seals conductors at entry to enclosure via conduit or enables an existing cable gland to be converted to a barrier type cable gland.
The device is fitted with a simple compound filled chamber which permits packing around individual insulated conductors. Assembly of the cable gland compresses and distributes the compound evenly to create a barrier seal at the point of entry into the enclosure. The compound chamber may be separated from the cured compound to ensure that the chamber has been effectively filled. If required, external voids can be repaired.
Provides female running coupler for cable gland or conduit entry.

 

 

 

 

 

 

Materials & Finishes

The CSB 656N cable gland is manufactured in Brass (standard), Nickel Plated Brass, 316 Stainless Steel or Aluminum. Brass NPT entries are nickel plated as standard.

 

Technical Data

1.Exd IIC Gb, Exe IIC Gb, Extb IIIC Db

2.Certificate No's Baseefa06ATEX0058X and IECEx BAS 06.0015X.

3.Suitable for use in: Zone 1, Zone 2, Zone 21, Zone 22 and in Gas Groups IIA, IIB and IIC.

4.Construction and Test Standards: IEC/EN 60079-0, IEC/EN 60079-1, IEC/EN 60079-7, IEC/EN 61241-0 and IEC/EN 61241-1.

5.Ingress Protection: IP66, IP67 and IP68 (30 metres for 7 days) to IEC/EN 60529 and NEMA 4X.

6.Deluge Protection to: DTS01

7.Operating Temperature Range: -60°C to +80°C

8.Assembly Instruction Sheet: AI 375.

 

CSB656N Spec.pdf

CSB656 Assembly.pdf

CSB656N Assembly.pdf

2.Hawke Accessories 2013 IDK.pdf

 

 

 

 

 

 

Hawke Ordering Format

[Gland Type/Size/Thread/Options]

Example : CSB 656N/C/M32/M32

 

 

 

  

 

 

내 기술지원 및 구매상담처

CUSTOMER SUCCESS IDK

deric@jadongwha.com

www.tiatip.com

 