호크 Hawke 710 Cable Gland/Connector 기술사양

 

안녕하세요 TIATIP 입니다.

 

Hawke의 American Series 가운데 Class 1 Division 2, Non-armoured TC- ITC, UL, ATEX approved을 갖추고 있는 710 Cable Gland/Connector를 살펴보도록 하겠습니다.

 

 

 

Hawke

Cable Glands

710 Cable Gland/Connector

American Series

Explosion Proof / IECEx and ATEX Approved Flameproof Exd /

Increased Safety Exe and Restricted Breathing ExnR

 

 

 

 

 

 

Features

Provides a barrier seal between the individual insulated conductors within the cable and prevents entry of the products of an explosion into the cable.
Assembly of the cable gland/connector compresses and distributes the compound evenly to effect a barrier seal at the point of entry into the enclosure.
Provides an outer deluge seal to prevent moisture ingress to the cable armour and enclosure. Deluge seal is colored red to indicate hazardous locations product.
Provides a cable retention and low smoke and fume, zero halogen seal onto the cables outer jacket.

 

 

 

 

Materials & Finishes

The 710 cable gland/connector is manufactured in Brass (standard), Nickel Plated Brass, 316 Stainless Steel or Aluminum. Brass NPT entries are nickel plated as standard.

 

 

Technical Data

 

1.UL Listing No: E84940.

2.Suitable for use in: Class 1, Division 2, Gas Groups A, B , C and D.
Class 1, Zone 2. Gas Groups IIA, IIB and IIC.
AExd IIC and AExe II Class 1, Zone 2.

3.Flameproof Exd, Increased Safety Exe ex logo II2 GD and Restricted Breathing ExnR ex logo II 3G

4.Certificate No's Sira 06ATEX1295X and IECEx Sir 06.0082X.

5.Suitable for use in: Zone 1, Zone 2, Zone 21, Zone 22 and in Gas Groups IIA, IIB and IIC.

6.Construction and Test Standards: UL 2225, IEC/EN 60079-0, IEC/EN 60079-1, IEC/EN 60079-7, IEC/EN 60079-15, IEC/EN 61241-0 and IEC/EN 61241-1.

7.Ingress Protection: IP66, IP67 and IP68 (30 metres for 7 days) to IEC/EN 60529 and NEMA 4X.

8.Deluge Protection to: DTS01

9.Operating Temperature Range: -50°C to +60°C (UL) and -60°C to +80°C (ATEX / IECEx)

10.Note: 710 cable glands are supplied dual ATEX/UL marked as standard.

11.Assembly Instruction Sheet: AI 316 (UL). AI 391 (ATEX / IECEx).

 