호크 Hawke 711 Cable Gland/Connector 기술사양

 

안녕하세요  TIATIP 입니다.

 

Hawke의 Americal Series NEC/IEC, Class 1 Division1, MCHL Armour, UL-ATEX Approved타입의 711 Cable Gland/Connector 를 살펴보도록 하겠습니다.

 

 

 

Hawke

Cable Glands

711 Cable Gland/Connector

American Series

Explosion Proof / IECEx and ATEX Approved Flameproof Exd

Increased Safety Exe and Restricted Breathing ExnR

 

 

 

 

Application

Outdoor or indoor use.
For use with continuous corrugated aluminum, Metal Clad (MCHL) cable.

 

 

 

 

 

 

Features

Provides 360° armour grounding which is fully inspectable.
Grounding device remains in contact with the cable when disassembled for inspection.
Provides a barrier seal between the individual insulated cores within the cable and prevents entry of the products of an explosion into the cable.
Assembly of the cable gland/connector compresses and distributes the compound evenly to create a barrier seal at the point of entry into the enclosure.
Provides an outer deluge seal to prevent moisture ingress to the cable armour and enclosure. Deluge seal is coloured red to indicate hazardous locations product.
Provides a cable retention and low smoke and fume, zero halogen seal onto the cables outer jacket.

 

Materials & Finishes

The 711 cable gland/connector is manufactured in Brass (standard), Nickel Plated Brass, 316 Stainless Steel or Aluminum. Brass NPT entries are nickel plated as standard.

 

 

 

 

Technical Data

 

1. UL Listing No: E84940.

2. Suitable for use in: Class 1, Division 1, Gas Groups A, B , C and D.
Class 1, Zone 2, Gas Groups IIA, IIB and IIC.
AExd IIC and AExe II Class 1, Zone 2.

3.Flameproof Exd, Increased Safety Exe ex logo II2 GD and Restricted Breathing ExnR ex logo II 3G

4.Certificate No's Sira 06ATEX1295X and IECEx Sir 06.0082X.

5.Suitable for use in: Zone 1, Zone 2, Zone 21, Zone 22 and in Gas Groups IIA, IIB and IIC.

6.Construction and Test Standards: UL 2225, IEC/EN 60079-0, IEC/EN 60079-1, IEC/EN 60079-7, IEC/EN 60079-15, IEC/EN 61241-0 and IEC/EN 61241-1.

7.Ingress Protection: IP66, IP67 and IP68 (30 metres for 7 days) to IEC/EN 60529 and NEMA 4X.

8.Deluge Protection to: DTS01

9.Operating Temperature Range: -50°C to +60°C (UL) and -60°C to +80°C (ATEX / IECEx)

10.Note: 711 cable glands are supplied dual ATEX/UL marked as standard.

11.Assembly Instruction Sheet: AI 317 (UL, Sizes A to F). AI 338 (UL, Size H). AI 389 (ATEX / IECEx).

 

1.Cable Glands-American Series NEC,IEC.pdf

2.Hawke Accessories 2013 IDK.pdf

 

 

 

 

Installation Guide

Hawke 711 Cable Gland/Connector

 

 

 

 

 

Hawke Ordering Format

[Gland Type/Size/Thread]

 

Example : 711/C/1"NPT

 

 

 

 

 

 

 

내 기술지원 및 구매상담처

CUSTOMER SUCCESS IDK

deric@jadongwha.com

www.tiatip.com

 

 

 