Hawke Cable Gland 321/R Series 기술사양 소개 (UPD20140611)

 

안녕하세요 TIATIP 입니다.

 

오늘 이 시간에는 2014년 06월 11일자로 업데이트된 호크 케이블글랜드 321/R 시리즈에 대한 사양에 대해 살펴보겠습니다.

 

 

 

 

HAWKE International

A Division of Hubbell Incorporated

Cable Glands

321/R Series

Hazardous Area

Increased Safety Exe

Class-Zones-Divisions

Certified ATEX/IECEx/cCSAus

 

 

 

 

Application
The 321/R cable gland provides a seal and cable clamp on the
outer cable sheath and is intended for use on non-armoured
elastomer and plastic insulated cables. The cable gland certifi ed
Exe and is suitable for installation in Zone 1 (21) and Zone 2 (22)
hazardous areas.

 

 

 

 

Technical Data

 

ATEX/IECEx
- Increased Safety Exe IIC Gb and Dust Extb IIIC Db II 2 GD.
- Certifi cate No’s: Baseefa06ATEX0059X and IECEx BAS 06.0016X.
- Suitable for use in Zone 1, Zone 2, Zone 21, Zone 22.
- Construction and Test Standards: IEC/EN 60079-0, IEC/EN 60079-7 and IEC/EN 60079-31.
- Ingress Protection: IP66, IP67 and IP 68 (30 metres for 7 days) to IEC/EN 60529 and NEMA 4X.
- Deluge Protection to DTS01.
- Operating Temperature Range: -60°C to +100°C.
- Assembly Instruction Sheet: AI 452.

 

cCSAus
- Increased Safety AExe IIC and Dust AExtD Zone 21.
- Explosion-proof Class 1 Division 2, Class II Division 2 Groups EFG, Class III.
- Certifi cate No’s: CSA1205533 for Marine Shipboard Cable.
- Construction and Test Standards: UL 60079-0, UL 60079-7, ISA 60079-31.
- CSA 22.2 No: 60079-0, CSA 22.2 No: 60079-7, CSA 22.2 No: 60079-31, UL 2225

 

 

 

 

Features
• When used in Increased Safety applications, this cable gland may be used with braided cable where the braid and the outer sheath pass into the enclosure. The braid must then be suitably terminated inside the enclosure.
Note: Braided cable is classed as unarmoured cable in the EN/IEC 60079 series standards for Exe applications.

• Manufactured in Brass (standard), Nickel Plated Brass, 316 Stainless Steel or Aluminium.

• Brass NPT entries are nickel plated as standard.

• Cable clamp provides required clamp and cleat function

 

Ordering Information
Format for ordering is as follows:
Certifi cation required i.e. ATEX / IECEx
Material & Finish i.e. Brass Nickel Plated
Alternative Seal (S), add suffix S to ordering information.

 

Example

321/R/C/M32/S/Nickel Plated Brass ATEX Certified

 

 

 

 

 

 

321R IDK Spec 20130129.pdf

321R IDK Spec 20140611.pdf

1.Hawke Accessories 2012 IDK.pdf

2.Hawke Accessories 2013 IDK.pdf

 

 

 

 

 

  

내 기술지원 및 구매상담처

CUSTOMER SUCCESS IDK

deric@jadongwha.com

www.tiatip.com

 

 

 

저작자 표시
신고
Posted by TIATIP

댓글을 달아주세요:: 네티켓은 기본, 스팸은 사절

Hawke Cable Gland 321 Series 기술사양 소개 (UPD20140611)

 

안녕하세요 TIATIP 입니다.

 

오늘 이 시간에는 2014년 06월 11일자로 업데이트된 호크 케이블글랜드 321 시리즈에 대한 사양에 대해 살펴보겠습니다.

 

 

HAWKE International

A Division of Hubbell Incorporated

Cable Glands

321 Series

Hazardous Area

Increased Safety Exe

Class-Zones-Divisions

Certified ATEX/IECEx/cCSAus

 

 

Application
The 321 cable gland provides a seal on the outer cable sheath and is
intended for use on non-armoured elastomer and plastic insulated
cables. The cable gland certifi ed Exe and is suitable for installation in
Zone 1 (21) and Zone 2 (22) hazardous areas.

 

 

 

 

Technical Data

 

ATEX/IECEx
- Increased Safety Exe IIC Gb and Dust Extb IIIC Db II 2 GD.
- Certifi cate No’s: Baseefa06ATEX0059X and IECEx BAS 06.0016X.
- Suitable for use in Zone 1, Zone 2, Zone 21, Zone 22.
- Construction and Test Standards: IEC/EN 60079-0, IEC/EN 60079-7 and IEC/EN 60079-31.
- Ingress Protection: IP66, IP67 and IP 68 (30 metres for 7 days) to IEC/EN 60529 and NEMA 4X.
- Deluge Protection to DTS01.
- Operating Temperature Range: -60°C to +100°C.
- Assembly Instruction Sheet: AI 451.

 

cCSAus
- Increased Safety AExe IIC and Dust AExtD Zone 21.
- Explosion-proof Class 1 Division 2, Class II Division 2 Groups EFG, Class III.
- Certifi cate No’s: CSA1205533 for Marine Shipboard Cable.
- Construction and Test Standards: UL 60079-0, UL 60079-7, ISA 60079-31.
- CSA 22.2 No: 60079-0, CSA 22.2 No: 60079-7, CSA 22.2 No: 60079-31, UL 2225

 

 

 

Features
• When used in Increased Safety applications, this cable gland may be used with braided cable where the braid and the outer sheath pass into the enclosure. The braid must then be suitably terminated inside the enclosure.
Note: Braided cable is classed as unarmoured cable in the EN/IEC 60079 series standards for Exe applications.

• Manufactured in Brass (standard), Nickel Plated Brass, 316 Stainless Steel or Aluminium.

• Brass NPT entries are nickel plated as standard.

 

 

Ordering Information
Format for ordering is as follows:
Certifi cation required i.e. ATEX / IECEx
Material & Finish i.e. Brass Nickel Plated
Alternative Seal (S), add suffix S to ordering information.

 

Example

321/C/M32/S/Nickel Plated Brass ATEX Certified

 

 

 

 

321 IDK Spec 20140611.pdf

321 IDK Spec 20110609.pdf

2.Hawke Accessories 2013 IDK.pdf

1.Hawke Accessories 2012 IDK.pdf

 

 

 

 

  

내 기술지원 및 구매상담처

CUSTOMER SUCCESS IDK

deric@jadongwha.com

www.tiatip.com

 

 

 

저작자 표시
신고
Posted by TIATIP

댓글을 달아주세요:: 네티켓은 기본, 스팸은 사절

Hawke 321 Cable Gland

 

안녕하세요?  TIATIP 입니다.

 

오늘은 Hawke 호크케이블그랜드 가운데 Increased Safety, Ex'e' 타입의 애플리케이션에 해당하는 제품인 Hawke 321 케이블그랜드를 소개합니다.

 

 

 

 

Hawke

Cable Glands
Hazardous Area
Increased Safety Exe
Dual Certified ATEX / IECEx

Hawke 321 Cable Gland

 

 

 

 

 

The 321 Cable Gland is only available from Hawke nternational distributor Stahl-Syberg.

 

 

 Hawke 321 Cable Gland

 

 

Application

The 321 cable gland provides a seal on the outer cable sheath and is intended for use on non-armoured elastomer and plastic insulated cables. The cable gland certifi ed Exe and is suitable for installation in Zone 1 (21) and Zone 2 (22) hazardous areas.

 

 

Features

• When used in Increased Safety applications, this cable gland may be used

   with braided cable where the braid and the outer sheath pass into the

   enclosure.

• The braid must then be suitably terminated inside the enclosure.
   Note: Braided cable is classed as unarmoured cable in the EN/IEC 60079

   series standards for Exe applications.

• Manufactured in Brass (standard), Nickel Plated Brass, 316 Stainless Steel or

   Aluminium.

• Brass NPT entries are nickel plated as standard.

 

 

Hawke Accessories for Cable Glands and Junction Boxes/Enclosures

 

 

 

 

Technical Data

• Increased Safety Exe II 2 GD ExtD A21.

• Certifi cate No’s: Baseefa06ATEX0059X and IECEx BAS 06.0016X.

• Suitable for use in Zone 1, Zone 2, Zone 21, Zone 22 and in Gas Groups IIA,

   IIB and IIC.

• Construction and Test Standards: IEC/EN 60079-0, IEC/EN 60079-7, IEC/EN

  61241-0 and IEC/EN 61241-1.

• Ingress Protection: IP66, IP67 and IP 68 (30 metres for 7 days) to IEC/EN

  60529 and NEMA 4X.

• Deluge Protection to DTS01.

• Operating Temperature Range: -60°C to +100°C.

• Assembly Instruction Sheet: AI 307.

• Alternative certifi cation options available:

 

 

 

 

품번예시(기본틀)

321/2K/M16,321/Os/M20,321/O/M20,321/A/M20,321/B/M25,321/C/M32,

321/C2/M40,321/D/M50,321/E/M63,321/F/M75,321/G/M80,321/H/M90,

321/J/M100,321/Os/1/2"NPT,321/O/1/2"NPT,321/A/3/4"NPT,321/A/1/2"NPT,

321/B/1"NPT,321/B/3/4"NPT,321/C/1-1/4"NPT,321/C/1"NPT,321/C2/1-1/2"NPT,

321/C2/1-1/4"NPT,321/D/2"NPT,321/D/1-1/2"NPT,321/E/2-1/2"NPT,

321/E/2"NPT,321/F/3"NPT,321/F/2-1/2"NPT,321/G/3-1/2"NPT,

321/H/3-1/2"NPT,321/J/4"NPT

 

 

 

 

Hawke Thread Conversion Solutions for Cable Glands and Junction Boxes/Enclosures

 

 

 

보다 자세한 사양(Technical Specification)은 다음의 세가지 첨부파일을 참고하시기 바랍니다.

 

 

321 IDK Spec 20110609.pdf

321 IDK Spec 20140611.pdf

321 Assembly 3.pdf

1.Cable Glands-Group ll.pdf

2.Hawke Accessories 2013 IDK.pdf

 

 

 

 

 

내 기술지원 및 구매상담처

CUSTOMER SUCCESS IDK

deric@jadongwha.com

www.tiatip.com

 

저작자 표시
신고

'TIEx > HAWKE' 카테고리의 다른 글

Hawke 153RAC Cable Gland의 주요특징 및 기술사양  (0) 2013.01.04
Hawke Cable Gland 악세서리모음  (0) 2012.12.18
Hawke 321 Cable Gland  (0) 2012.12.18
Hawke SB474 Cable Gland  (0) 2012.12.18
Hawke PSG553RAC Cable Gland  (0) 2012.12.18
Hawke ICG653Universal/L Cable Gland  (0) 2012.12.18
Posted by TIATIP

댓글을 달아주세요:: 네티켓은 기본, 스팸은 사절


BLOG main image
by TIATIP

카테고리

TI Story (957)N
TIA (92)
TIP (194)
TIEx (601)N
TIS (36)
TIO (23)
TiNoTe (10)
The OtherS (1)