Hawke 호크 Enclosure PL-Range GRP Series, PL712 Type Junction Box
안녕하세요 TIATIP 입니다.
오늘은 Hawke 호크 GRP 박스로 대표되는 PL Range 가운데 PL712 타입에 대해 살펴보겠습니다.
Hawke 호크 PL712 GRP Juction Box
Hawke Enclosure Type : PL712
Glass Reinforced Polyester
Exe Enclosures for Harsh and Hazardous Locations
The Dual ATEX/IECEx Approved PL712 Enclosure
호크
Hawke 호크 PL712 GRP Juction Box
Hawke Junction Boxes
Technical Data
Increased Safety II 2 GD Exe IIC Gb, Extb IIIC Db.
PL712 Certificates:
Baseefa Certificate No. Baseefa08ATEX0272X.
IECEx Certificate No. IECEx BAS 08.0091X.
ZPL712 Certificates:
Baseefa Certificate No. Baseefa08ATEX0271U.
IECEx Certificate No. IECEx BAS 08.0090U.
Suitable for use in Zone 1, Zone 2, Zone 21 and Zone 22.
Construction and Test Standards:
IEC/EN 60079-0, IEC/EN 60079-7, IEC/EN 60079-31.
Ingress Protection: IP66 to IEC/EN 60529.
Deluge protection to DTS01.
Operating Temperature Range: -60°C to +75°C.
Temperature Class and Ambient: T6 40°C,
optional T5 with ambients up to 65°C.
Hawke 호크 PL712 GRP Juction Box
Please Note :
Hawke still offer enclosures to customer specifications available from our Box Modifiers.
An earth terminal equal to that of the largest power terminal will be fitted.
The terminals listed are restricted to a minimum operating temperature of -50°C.
Hawke 호크 PL712 GRP Juction Box
Materials And Finishes
Glass Reinforced Polyester. Natural Black Finish.
Flame Retardant to IEC 92.1 Clause 2.38
Hawke 호크 PL712 GRP Juction Box
General Information
Standard PL712 Enclosures are supplied complete with:
Integral Steel Earth Continuity Plate.
1 x M20 tapped entry per face (entries not plugged).
General Information
1. The Ultimate in Robust GRP Construction
Designed to withstand impact resistance up to 20Nm for PL6 series (7Nm for PL7 series). GRP construction provides a high degree of resistance to corrosive atmospheres.
2. Anti-Static Properties Removes the risk of ignition sources through static
induced sparking resistivity. Insulation resistance less than 1GΩ.
3. External Mounting Feet Eliminates the need to remove the lid when
mounting the enclosure on the wall.
4. Earth Continuity Plate Optional.
5. Stainless Steel Rating Label Highly durable and corrosion resistant.
6. Corrosion Resistant Stainless Steel Lid
Fixing Screws with Nylon Retaining Washers Prevents loss of screws during assembly and maintenance.
7. One Piece Durable Captive Moulded Silicone Gasket
DTS01 deluge protection. Provides Ingress Protection to IP66 and IP67.
Optimum performance at low and high temperature extremes.