Hawke 753 Cable Gland/Connector

 

 

안녕하세요 TIATIP 입니다.

 

오늘은 호크 케이블그랜드 가운데 North American Cable Glands/Connectors 753 시리즈에 대하여 알아봅니다.

 

 

 

 

Application

Outdoor or indoor use.
For use with braid armoured marine shipboard jacketed or non-jacketed cable.

 

Features

Provides a barrier seal between the individual insulated conductors within the cable and prevents entry of the products of an explosion into the cable.
Assembly of the cable gland/connector compresses and distributes the compound evenly to effect a barrier seal at the point of entry into the enclosure.
Provides an outer deluge seal to prevent moisture ingress to the cable armour and enclosure. Deluge seal is coloured red to indicate hazardous locations product.
Provides a cable retention and low smoke and fume, zero halogen seal onto the cables outer jacket.

 

 

 

Materials & Finishes

The 753 cable gland/connector is manufactured in Brass (standard), Nickel Plated Brass, 316 Stainless Steel or Aluminum.
Brass NPT entries are nickel plated as standard.

 

Technical Data

UL Certificate E84941.
Suitable for use in:
Class 1, Division 1, Gas Groups A, B, C and D.
Class 1, Zone 2, Gas Groups IIA, IIB and IIC.
AExd IIC and AExe II Class 1, Zone 2.
Flameproof Exd, Increased Safety Exe  II 2 GD and Restricted Breathing ExnR  II 3G.
Sira Certificate No. Sira 06ATEX1295X
IECEx Certificate NO. IECEx Sir 06.0082X
Suitable for use in Zone 1, Zone 2, Zone 21, Zone 22 and in Gas Groups IIA, IIB and IIC.
Construction and Test Standards: UL 2225, IEC/EN 60079-0, IEC/EN 60079-1, EC/EN 60079-7, IEC/EN 60079-15, IEC/EN 61241-0 and IEC/EN 61241-1.
Ingress Protection: IP66, IP67 and IP 68 (30 metres for 7 days) to IEC/EN 60529 and NEMA 4X.
Deluge protection to DTS01.
Operating Temperature Range: -50°C to +60°C (UL) and -60°C to +80°C (ATEX / IECEx).
Note: 753 cable glands are supplied dual ATEX/UL marked as standard.

 

 

 

 

 

국내 기술지원 및 상담구매처

CUSTOMER SUCCESS IDK

deric@jadongwha.com

www.tiatip.com 

 

'TIEx > HAWKE' 카테고리의 다른 글

Hawke 153/X Cable Gland/Connector  (0) 2013.05.30
Hawke 755 Cable Gland/Connector  (0) 2013.05.30
Hawke 713 Cable Gland/Connector  (0) 2013.05.30
Hawke 710 Cable Gland/Connector  (0) 2013.05.30
Metal Clad (MCHL) cable 용 Hawke 711 Series  (0) 2013.05.30

+ Recent posts